Article
|
Revamping Duesseldorf
The following article appeared in
NFPA Journal Online. ©
2002 NFPA Journal Reprinted with permission.
In
1996, a catastrophic fire at Dusseldorf International Airport in
Germany killed 17 people and injured 87 others.
When the new terminal opened last summer, significant changes,
prompted by that fire, had been made? Ed Comeau traveled
back to Germany to find out.
On April 11, 1996, a catastrophic fire broke out
at the Duesseldorf, Germany airport terminal.
This fire claimed the lives of 17 people, and is the only fire
in an airport terminal that claimed civilian lives, according to
research done by the NFPA.
The NFPA sent Chief Fire Investigator Ed Comeau
to Düsseldorf to document this tragic fire.
At the same time, the British Airport Authority (BAA) dispatched
a team of investigators, which included Divisional
Officer David
Whittington. Both the NFPA
and BAA published reports based on the information that was available
at the time. This article
is going to look at some of the information that has emerged following
the publication of these reports, as well as changes that have taken
place at Düsseldorf Airport. Both
Comeau and Whittington traveled to Düsseldorf Airport and met with
several officials in compiling this article.
The Fire
According to a report published by the
Independent Expert Committee for the Investigation of the Düsseldorf
Airport Fire on 11 April 1996, the fire was started by welding
operations. A welder was working on a roadway expansion joint that was
located over the ground floor void space.
The sparks generated by the welding fell into the open joint and
came into contact with rubber-like sheets that had been installed to
divert water. According to
tests conducted by the Committee, these sheets were classified as
“normally flammable,” and it was theorized that they were the
material that was first ignited.
Within the void space below the area where the
welding was occurring was combustible thermal insulation that was
attached to the underside of the concrete deck.
This insulation, which measured 60 mm (2.4 inches) thick, was
composed of polystyrene rigid foam.
The Committee believes that the burning rubber-like sheets
caused the polystyrene foam boards to melt and then ignite, providing
further fuel for the fire.
Because there was no smoke detection in the void
space, nor below it in the occupied space, the fire was not detected
until it was well developed. The
first alarm came from a taxi driver at 15:31 hours (3:31 p.m.) who
observed sparks falling from the ceiling.
This person notified the airport fire brigade, who dispatched
two members to investigate. When
they arrive two minutes later, no smoke was observed on the ground
floor.
However, on the first floor, some people had
observed smoke on this level. It
was assumed that the smoke had migrated up a stairwell to this floor.
After investigating the incident for
approximately 15 minutes, the two fire fighters who had originally been
dispatched requested additional resources.
Because of the size of the fire and the large area involved in
the fire, fire fighting operations were difficult, and the fire was not
brought under control until approximately 19:20 hours (7:20 p.m.).
At the time of the fire there were approximately
2,000 people in the building. Eighty-seven
were injured, two seriously, and seventeen people were killed by smoke
inhalation.
Seven people were killed in the Air France
lounge that was located two levels above the fire and on the opposite
side of the terminal building, and one person was killed on the
stairway leading to the lounge. Another
seven people were killed in elevators that opened into the fire area.
One person was found dead in a lavatory.
According to the Committee’s report, there was
a total of 24,000 kg (53,000 pounds) of combustible fuel.
Approximately 47%, or 11,400 kg (25,100 pounds) of this was
comprised of polystyrene, while 24% (5,900 kg (13,000 pounds)) was PVC
cable insulation.
The committee’s report addressed how
significant a factor the PVC cable insulation was in the spread of the
fire.
“It is difficult to
determine in retrospect how the cables contributed to the spread of the
fire – whether is would have spread to a similar extent without the
supporting combustion of the PS rigid foam, or whether a local initial
fire would have ceased due to the combustion properties of PVC.
However, it can surely be stated that even common cables
‘containing no halogen and with a more favourable reaction to fire’
would have been burnt completely due to the combustion of the PS rigid
foam. The application of
fire retardants would not have resulted in an essentially better
reaction to the terminal fire on April 11th, 1996.”
According to Dr. Adrian Beard, who worked on the
committee, 11 people were charged following the fire.
They included the welder, airport building officers, and staff
from the airport and Düsseldorf fire brigades.
Findings of the government study
There were several significant contributing
factors to the fatalities identified in the committee’s and the
official NFPA fire investigation report.
-
In the Air France lounge, both exits from the
lounge discharged into the same air space, which was contaminated by
the smoke. Furthermore, the lounge’s windows were not exterior
windows, but were separated from the exterior windows by a space of
70 cm (28 inches). Because
of this, these windows could not have successfully been used to
escape from the lounge, where seven people were killed.
-
The seven people that were killed in two
different elevators died because the elevators opened on the fire
floor. Because of the
density of the smoke, the doors would not close, nor were the
occupants able to see any of the exits in the area.
Even though they were able to make emergency calls to the
technical control center, advising them of their plight, this
information was not passed on to the fire department quickly enough
for them to be rescued.
Other factors identified in the NFPA Fire
Investigations report that contributed to the severity of the incident
included:
-
Improper voice evacuation instructions were
given during the initial stages of evacuation, delaying movement of
people out of the building.
-
Delayed fire department response to the fire
-
Use of significant amounts of combustible
material in an unprotected void space
-
Lack of coordination between the airport fire
brigade and the municipal fire brigade
-
Communications difficulties among fire
fighting units
Changes that have occurred
Given the magnitude of the tragedy in terms of
life loss and property damage, the airport authority undertook efforts
to ensure that such an incident would not occur again.
A number of changes were made in the design of the building, its
systems, staffing, operating procedures and training operations.
These include:
-
Installation of sprinkler systems throughout
the terminal building.
-
Dramatic upgrade of the fire alarm system.
-
Staffing of the airport and municipal fire
brigades
-
The creation of a fire prevention division
within the airport
-
Development of a comprehensive emergency
response plan.
In 1997, a fire prevention division comprised of
four fire protection engineers was established, including Stefan
Bunthoff, head of Fire Prevention.
According to Bunthoff, the are four principles
that are part of the fire safety strategy employed at the Düsseldorf
Airport. They include:
-
Avoiding the occurrence of fire
-
Preventing the spread of fire and smoke
-
Rescuing people and animals
-
The performance of effective fire fighting.
Building Design
Because the fire originated in a combustible
void space that was hidden from view, the designers wanted to allay any
fears that the traveling public may have about this type of
construction. For that
reason, according to Bunthoff, the new design incorporates a completely
open ceiling plan, with all of the structural elements and utilities
exposed to view.
The use of the materials used in the
construction of the building and its fixtures is closely regulated,
according to Bunthoff. They
attempt to minimize the fire load of fixtures such as counters, which
are often made of metal instead of combustible materials.
Upholstered furniture located in the concourse, must been the
requirements of DIN-EN standard 1021.
Insulation material must also meet a DIN standard for
combustibility.
Compartmentalization is used throughout the
terminal to limit the spread of any toxic smoke or fire.
In the 1996 incident, both were able to spread far beyond the
original area of origin, killing people that were located several
floors above the fire. To
avoid this happening again, the current terminal is divided into fire
and smoke sectors. This is
accomplished by mechanisms such as doors that will automatically close,
subdividing areas into these compartments.
Within the concourse are a number of shops that
could have a large combustible fuel load because of their inventory.
Some of these shops are located in the middle of the concourse,
away from the perimeter walls and are essentially “stand-alone”
units. A concept called a
“box cap” system is employed in an effort to provide a level of
protection within these units.
Each unit is equipped with a fire sprinkler
system at the roof level. In
addition, each unit also has a smoke extraction system that will
discharge any smoke logged air to the exterior of the building.
The upper 60 to 70 cm (24 to 28 inches) of the store is equipped
with a “cap” that will serve to contain the smoke-filled air and
also help to concentrate the heat, allowing for an earlier activation
of the sprinkler system than may otherwise be possible.
The doors to the units are security grills, which allow for air
to enter into the unit even if it is closed.
Fire Alarm System
The current fire alarm system is comprised of
the following elements:
-
3,300 smoke detectors
-
180 manual pull stations
-
50 air aspirating smoke detectors
-
20 linear infrared (IR) smoke detectors
-
2,800 loudspeakers
There are eight graphic annunciator panels
located throughout the terminal complex.
Each one is identical in design and provides the fire brigade
with the ability to control a number of functions, as well as identify
where the alarm signals are originating.
The fire alarm system interfaces with the
following systems:
-
47 smoke extraction ventilators
-
35 elevators
-
Air supply windows and doors
-
Smoke exhaust vents
In the event of fire alarm system activation, a
specific sequence of events occurs.
If a single smoke detector is activated in any
area, or if a sprinkler system or smoke detector in a box cap store is
activated, a signal is sent to the airport terminal control center and
to the airport fire brigade watch center.
A terminal staff member is dispatched to investigate the cause
of the activation.
However, if two smoke detectors or a manual pull
station are activated, then the airport fire brigade is dispatched
immediately. The
pre-recorded evacuation announcement begins.
This announcement is repeated in four languages (German,
English, French and Turkish). An
alert signal is given first, then the voice recording, and then another
alert signal is sounded before the recording is repeated in the next
language. Each message is
about 30 seconds long, according to Bunthoff.
However, there are some exceptions throughout
the terminal, said David Harriman, Head
of Aviation Security and Emergency Planning.
In some areas, such as the office mezzanine, the building fire
alarm system is activated if a single smoke detector is placed into
alarm. This decision was
made after evaluating the risk in that particular area and determining
the safest course of action.
Furthermore, some of the larger terminal areas
are not automatically placed into full alarm.
In the departure area, for example, if two smoke detectors are
activated, the fire brigade will respond and evaluate the conditions.
They will then make the decision as to whether to manually
activated the evacuation signal or not.
SIDEBAR: The message that is played is:
“Ladies and Gentlemen, your attention please.
Due to an unexpected incident we must evacuate this terminal
building. Please leave the
building now following the emergency exit signs, remain calm and help
anyone in difficulty. Do
not use elevators or escalators. Please
follow the instructions of the security staff.”
Some other actions that automatically occur when
the building fire alarm system is activated include:
-
Fire and smoke control doors are
automatically closed
-
Any emergency evacuation doors that are
locked are automatically unlocked.
-
Smoke extraction systems are activated
-
Doors and windows are automatically opened to
provide fresh makeup air for the smoke extraction system
-
The air conditioning systems are
automatically shut down
-
Baggage belts and escalators are shut down.
In the 1996 fire, seven people were killed when
the elevators they were using opened on the fire floor. They were not able to escape, and the doors would not close
because the smoke obscured the door’s photoelectric eye.
To avoid a similar tragedy, the elevators now
interface with the fire alarm system.
If the building’s fire alarm system should be activated, the
elevators automatically travel to the ground floor, where the doors
open. A recording advises the passengers that the elevator is out
of service, and the doors remain open.
If a smoke detector on the ground floor should
be activated by smoke in the area of the elevators, then the elevator
car stops at the first floor, where the passengers can safely escape.
Evacuation
A review was undertaken of the different
evacuation routes throughout the terminal.
To help facilitate moving people there are a number of doors,
which are normally closed and locked, that will automatically swing
open, creating escape routes. Some
of these routes discharge passengers onto the exterior of the building
on the airside, but this is not a significant concern to the aviation
authorities, said Harriman. For the drills, those that evacuate to the airside do not
have to pass back through security.
However, if it were a real incident, they probably would have
to, according to Harriman.
There are 37 assembly points located throughout
the airport grounds. Uniformed
supervisors that are on site 24 hours a day have been identified and
assigned to particular assembly points.
Harriman said that it is important that they are uniformed
because the public is more willing to take direction from someone in
uniform versus civilian clothing.
Complete evacuation drills are conducted once a
year in the terminals during normal operating hours.
This is coordinated with the airport tower to occur during a
time when there are not planes arriving or departing, which generally
means there is a 30 minute window of opportunity in which to carry out
these drills.
In 1997, the first full evacuation drill
involving the public was undertaken.
According to Harriman, there was a lot of resistance from within
the organization to doing such an exercise.
The only other airport that he was aware of that had done a
drill involving the public was Dublin airport.
Management eventually agreed to conduct the drill once they
realized its importance.
A fire was simulated in the British Airways
lounge by using a smoke generator.
It was estimated that there were about 1,700 people in the
building, and it was evacuated within 9 minutes.
Passengers were directed to the assembly points located
throughout the airport. Those that had already passed through security were taken
outside on the airside of the building.
Harriman observed that business travelers, who
were familiar with the building, had a tendency to evacuate via the
same route that they entered. Holiday
travelers, however, who were not as familiar with the building, did
tend to use the nearest exit.
When the videotape of the drill was later
analyzed, it was noticed that many people did not evacuate until
prompted by airport staff. For
this reason, management felt that they needed to train more airport
staff in evacuation procedures. Fire
safety training is going to become a part of the training program when
employees get badges to work on the airside of the terminal operations.
In addition, when the new Terminal B opens, the
concessionaires’ employees will all be required to attend the fire
safety training as part of their contracts.
There was also a problem with the voice
annunciation system. All
of the different zones in the terminal work off of the same voice
annunciation system. Therefore,
if a particular zone should go into alarm later in the incident, the
voice annunciation for that zone is going to pick up mid-stream of the
original message. According
to Harriman, by the time the later zones were going into alarm, the
voice annunciation system was playing the English message.
Because of this, employees are trained to focus on the fact that
the alarm has been activated and that the siren is sounding and to not
focus on the particular words of the message.
In 2000, another drill was planned.
The planners attempted to conduct this drill without letting the
airport staff know when they are going to occur in order to maximize
its effectiveness in evaluating people’s behavior.
Employees and concessionaires were advised that it would occur
sometime between November 1 and December 15, but were not provided with
any more details. However,
word of the drill’s specific date and time started to spread, and
companies were adjusting their rosters to ensure that their best people
were on duty, according to Harriman.
When it became apparent that people knew when the drill was
going to be held, the decision was immediately made to move it up a day
earlier.
One of the adjustments they made in this drill,
based on prior experience, was allowing the shops to keep one person in
the store. When they had
completely evacuated the terminal during a previous drill, one of the
concessionaires had to undertake a complete inventory, which was a
time-consuming and arduous task.
There was some concern as to whether passengers
would leave their luggage behind when they evacuated, creating a
potential security risk. However,
that was not the case. Also,
restaurants were very cooperative and said they would provide
replacement food or drinks to any customer that requested it.
Overall, the response to the drill was positive and there were
significant lessons that were learned from this exercise.
Sprinklers
At the time of the fire the buildings were not
equipped with fire sprinkler systems.
The fire broke out in a void space that contained combustible
insulation, which served as a fuel and spread the fire throughout the
void space. Obviously, sprinklers in this area would have made a
difference in terms of controlling or suppressing the fire.
Sprinklers have now been installed throughout
the airport terminal buildings. With
the open ceiling plan, these systems are very prominently seen
throughout the terminal building.
According to Bunthoff, to provide sprinkler
protection in the new main terminal and in Pier B, they utilize 6
electrically powered fire pumps. Each
pump can discharge 3,000 lpm (793 gpm) at 9 bar (131 psi).
There is a total of 70,000 meters (230,000 feet)
of sprinkler piping in the terminal, supplying 17,500 sprinkler heads.
Bunthoff reports that the discharge out of the sprinklers is 5
lpm over 1 m2 (0.123 gpm/ft2).
Airport Fire Brigade Operations
At the time of the fire, the authorized staffing
level of the airport fire brigade was 77 people.
As a result of the fire, according to Head of Firefighting Thomas
Jeziorek, staffing levels have been increased to 136 fire fighters,
with 22 fire fighters on each shift.
A new watch room, staffed 24 hours a day by two
fire fighters, monitors all of the airports fire alarm and suppression
systems. They are able to
remotely place smoke detectors out of service from the watch room, as
well as communicate with the fire apparatus.
Since the cause of the 1996 fire was related to
welding, a new hotworks permit program has been instituted. Before undertaking any work, the worker or contractor has to
fill out paperwork and conduct a risk assessment.
The plan of work is then taken to the fire department, which
then checks to ensure they have fire extinguishers and other safety
equipment in place. The
contractor is then responsible for providing proper protection at the
site and when finished, must take the paperwork back to airport control
to indicate they are done. If
a contractor should cause an unwanted alarm because of hotworks, they
are fined 2,500 German marks (approximately $1,000 U.S. dollars).
In addition to its complement of ARFF apparatus,
the airport brigade is now equipped with two structural fire fighting
apparatus, one staffed with five fire fighters and the other with
three. Because of the
on-duty staffing (22 fire fighters), they are able to respond to
structural fires using these two pieces of apparatus without reducing
the level of ARFF response below that required by the aviation
authorities.
Düsseldorf municipal fire brigade
Changes have occurred with the Düsseldorf
municipal fire brigade as well following the fire.
According to Peter Albers, a chief officer with the Düsseldorf
municipal fire brigade, staffing has increased from 500 to 580 fire
fighters. In addition,
three of the stations in the vicinity of the airport have added an
additional fire engine.
Albers also reported that prior to the fire
there were no standard operating plans for a response.
As a result of the fire, they have established protocols that
range from F1 (low) to F4 (highest level of response).
There were problems with coordinating the
operations of the municipal fire brigade and the airport fire brigade. Prior to the fire, and currently, the two brigades do not
regularly train together except for one major exercise a year.
To help in coordinating their operations, a single Incident
Coordination Center has been established.
The purpose of the ICC is to bring together the multitude of
different agencies and departments that need to be working together
during an emergency.
Radio communications was a problem for the
municipal fire brigade during the fire, and still is today.
In large buildings, such as the airport terminal, they may have
to set up relays to transmit messages between various units. However, there is now a common radio frequency that is shared
by the municipal and airport fire brigades.
Emergency Operations Plan
According to Albers, the Düsseldorf Fire
Brigade is responsible for reviewing and approving building
construction plans for the airport.
One requirement that they instituted was that the airport have
an emergency response plan before they would agree to approve any
building construction. They knew that if the plans were approved before this plan
was developed that it would probably never happen.
In 1997, Harriman, was tasked with developing
the emergency response plan. The
one that the airport had in place only addressed aircraft emergencies
and did not include building incidents.
He started reviewing plans from other airports in Germany, and
only one other airport had one that he considered credible.
A working group was formed to develop a plan
specifically for Düsseldorf. Part
of the objective by forming this group was to get the plan accepted at
all levels within the organization.
Because of the variety of operations and buildings at the
airport, it was necessary to develop a separate evacuation plan for
each building rather than a general one that could be applied
airport-wide.
Düsseldorf Today
The Düsseldorf airport now has a comprehensive
system of suppression, detection and evacuation in place to avoid a
repetition of the tragedy that struck in 1996.
As the only airport that has ever suffered a tragedy of this
magnitude, they want to ensure that it does not happen again.
According to officials, the changes that have been made in the
fire protection systems and operating plans are steps in that
direction.
Ed Comeau is the principal writer for
writer-tech.com. He is the
former chief fire investigator for the NFPA and investigated the 1996 Düsseldorf
airport terminal fire.
David Whittington is a divisional officer and
senior airport fire officer for the British Airport Authority. He also investigated the 1996 fire and worked with NFPA in
compiling information for both the NFPA report and for this article.
|