Article
|
Capitol Challenge
Protecting the Capitol means dealing with a
historic building filled with priceless artwork and Congress, which
can’t be interrupted for every renovation.
The
following article appeared in the November/December, 2000,
issue of NFPA Journal.
©2000 NFPA Journal. Used with
permission
The United States Capitol, one of the most
enduring symbols of the U.S. government, is rich in history and serves
as a museum for some of our nation’s most important works of art.
Along with this cultural heritage, it also houses the Senate and House
of Representatives. Combining a historical building, a museum, and an
office building into one structure provides some significant challenges
when designing and installing fire protection.
Construction on the United States Capitol began
in 1793, and the Congress, the Supreme Court, the Library of Congress,
and the courts of the District of Columbia occupied the north wing in
1800. Construction stopped until additional funding in 1803 allowed the
government to hire architect Benjamin Latrobe. As work began on the
south wing, the north wing, which was already falling into disrepair,
needed renovations. This work was only partially completed by 1811,
when funding became scarce because of the impending war with Great
Britain.
However, even then fire safety was in the
forefront, according to Bill Allen, architectural historian for the
Architect of the Capitol.
“[Being] fireproof and solid were two of the
driving forces,” says Allen. “Latrobe was using construction
methods involving masonry arches and domes. Not only were these
architecturally pleasing, they were some of the best-known fire safe
construction methods of the time.”
Latrobe’s good sense was put to the test in
1814 when the British set fire to the Capitol and the White House
during the War of 1812. According to Allen, the fire heavily damaged
the White House, which was built primarily of wood. The Capitol
building, on the other hand, suffered less fire damage.
After the war, Charles Bullfinch, a Boston
architect, began to oversee the construction. By 1826, 33 years after
construction originally started, the Capitol was complete, sporting a
copper-covered wooden dome over the center of the building.
By 1851, however, the government was outgrowing
the building and expansion started on the north and south wings. After
the renovation, the dome wasn’t proportional to the length of the
wings and was also considered a fire hazard. In 1856, the old dome was
removed, and a “fireproof” cast-iron dome was put in its place.
The Capitol building, which itself is considered
a historical work of art, is home to numerous priceless works of art
that document important events in U.S. history. The Rotunda is home to
the Declaration of Independence, as well as three paintings by John
Trumbull, which were put in place between 1819 and 1824. Between 1840
and 1855, additional paintings were added, and in 1865, Constantino
Brumidi painted “The Apotheosis of Washington” on the dome’s
canopy. Other works of art in the Rotunda include statues and busts of
presidents, including George Washington, Abraham Lincoln, Ulysses
Grant, and Thomas Jefferson.
Fire protection
“One of the unique challenges is the ability
to design and install fixed detection or suppression systems while not
destroying the architectural fabric of the building,” says Ken
Lauziere, P.E., head of the Fire Protection Engineering Division for
the Architect of the Capitol (AOC). Lauziere, who’s been designing
fire protection systems for the Capitol for 22 years, has had a lot of
experience overcoming these challenges.
Balancing the needs of fire protection against
preserving the historical heritage is an ongoing effort in the Capitol.
“We use a lot of creative thinking and
creative use of existing technologies,” says Lauziere. “How do you
install wiring without it destroying wall murals painted in the 1860s,
for instance?” Some of the methods used are unique. Take, for
example, some special pieces of art that merit different suppression
systems. The cases that hold the Maintz Bible and other valuable works
use gaseous agents and cross-zoned smoke detection. These systems
currently use Halon 1301, although newer systems are using
environmentally compatible agents. Sprinklers back up these gaseous
agent systems.
It’s also important to protect the 30,000
daily visitors and the 35,000 Capitol employees. Any interruptions to
sessions of Congress are taken very seriously, so it’s vital to
identify potential fires early and initiate an appropriate response.
Once a fire protection need is identified, the
AOC’s office puts together a cost estimate. These requests must go
through a series of hearings before a subcommittee responsible for
legislative branch appropriations. If the committee agrees, the funding
for the design and installation is available two years later.
A major hurdle for the AOC is scheduling the
work. Each congressional representative and senator’s office is
“owned” by the state he or she represents, and the AOC can only do
work with the occupant’s permission. Furthermore, much of the work is
done at night or while Congress is in recess to minimize interruption.
When work in a particular office is being done,
a photograph is taken immediately before the work begins. Then, when
the crew has finished for the night, it uses the photograph as a guide
to replace all the furnishings to their original positions.
Photographs are also taken of the work in
progress. After the workers channel a wall through which they’re
going to run wiring, for example, they take a picture. Later, if an
office needs to be modified, they can check to see if the work will
affect any wiring.
More logistical problems come from having to do
the work in small sections.
“We can’t do a whole wing, and go left to
right. We have to do one room at a time, channel it, wire it, and then
do the next room,” says Bob Creger, supervisor field representative
for the Construction Branch of the AOC.
Smoke detection
According to Creger, the building has various
types of smoke detection systems. Approximately 90 percent of the
systems use conventional smoke detectors, while 8 percent use beam
detectors, and the remaining 2 percent use air-sampling systems.
Air-sampling systems are installed in some of
the rooms that contain artwork. In one of the hearing rooms where
Brumidi painted the walls, for example, the AOC installed piping up a
doorway through which they draw air samples. To complete the
installation, the floor tiles had to be removed and the piping run to a
sampling device in the basement. The piping was so well concealed that
the committee chairman couldn’t even find the smoke detection in the
room.
Lauziere also uses projected beam smoke
detection. By installing the equipment on the tops of column caps,
where it can’t be seen from below, they’re able to cover vast areas
with minimal detection. This protection scheme is typically used in the
large hearing rooms, most of the corridors, and in the great halls. In
the Rotunda, the detectors are at three different levels and calibrated
to detect obstruction levels of 3 to 6 percent per foot.
Currently, the AOC is providing smoke detection
in the Capitol dome itself, which is actually two separate structures,
one inside the other. Within this interstitial space, the AOC is
installing air-sampling tubes to draw in air and carry it to a sampling
location. An air sampling laser smoke detector then tests the air for
smoke particles.
While this system could detect a small fire in a
wastebasket on the floor of the Rotunda, Lauziere says that the a fire
would probably be detected even sooner by other means. Such means
include Capitol police officers who are positioned throughout the
building when the Capitol is open. Furthermore, an extensive network of
video cameras monitors many areas of the building, helping to spot
fires in their early stages.
Because of the design of the building, the
second floor is the most challenging to retrofit, according to Creger.
If fire alarm systems are installed on the first or third floors,
wiring can be run in the basement or the attic. Since this isn’t
possible on the second floor, more creative measures have to be used.
Sprinklers
Recently, there’s been a push to install
sprinkler systems throughout the Capitol complex. Lauziere has used
such techniques as designing almost every sprinkler system as a looped
system.
“The advantage is that this not only provides
us with redundancy, but we’re able to use a smaller pipe diameter,
too,” he says. The AOC also makes extensive use of copper piping in
the sprinkler systems because of the pipe’s smoother flow
characteristics. Copper piping is easier to work with and conceal, as
well.
Installing sprinklers so that they’re not in
plain view is another significant challenge. One common technique is
placing a sprinkler in the middle of a decorative rosette. However,
before any workers drill into the middle of an actual rosette, they use
practice rosettes to demonstrate that they can do the work without
causing damage. In some rooms, they’ve installed the piping along
wall molding and painted it to blend in. For consistency, they’ve
even installed piping along the room’s other three walls.
“Sprinklers in some of the buildings are so
well concealed that without drawings, I can’t find them,” says
Lauziere.
Workers have also had to use unusual techniques
to drill holes. In one case, Lauziere had the contractor cut a hole by
running the saw in reverse to wear away the plaster instead of cutting
it, which would have caused more damage.
“The contractor thought I was crazy,” says
Lauziere.
Since the occupancy use of an area can change
frequently, each of the systems is designed for ordinary Group II
sprinkler densities. By doing so, Lauziere knows that the sprinkler
system can provide protection for any future use.
Lauziere has also had to install sprinklers
contrary to their UL listing. For example, he’s placed quick response
sprinklers lower than their listing calls for. Testing at the National
Institute of Standard and Technology has shown that doing so causes the
quick response sprinkler to react like a standard response sprinkler,
which was his intended goal. At a recent fire in one of the house
office buildings, “everything worked as it was supposed to,” says
Lauziere. “This keeps validating that the systems are working.”
Lauziere has conducted live burns to test some
of the designs, and he uses computer modeling, as well.
Fire alarms and egress issues
In 1980, the AOC decided to put in a slow whoop
signal fire alarm system. The main reason was that it emits a
distinctive sound that only the alarm system would make. The system can
also reproduce voices, so it can give directions. At first, the system
used taped messages but now uses digitized messages. All the fire
control rooms and the police division offices can also give live
direction through microphone input.
One unique design feature in the fire alarm
system is that no device can activate the audible devices. Instead, an
alarm signal is transmitted to one of the constantly monitored
locations in the complex, and an on-duty Capitol police officer is
immediately dispatched to evaluate the situation. This procedure avoids
malicious activations of the system while Congress is in session. This
method works because police constantly staff the building, which has a
significant number of video cameras.
One
of the reasons egress design is a challenge, says Lauziere, is because
stairways were converted to elevator shafts when the building was
retrofitted with elevators, and alternative egress routes weren’t
created to make up for the lack of stairs. To help correct some of the
deficiencies, the AOC has sometimes had to come up with unorthodox
solutions. For example, they’re currently converting an exterior
window into a door.
Because of the Capitol’s design, it’s not
possible to compartmentalize the building. If a general evacuation is
necessary, the entire building is evacuated at the same time.
The Capitol police are an integral part of the
evacuation process. Since they’re required to conduct evacuation
drills for each building under their jurisdiction, they conduct drills
at least 14 times a year. This, according to Lauziere, has provided
them with a great deal of experience in managing mass evacuations.
What to do?
When undertaking any fire protection project in
a historic building, putting together a team composed of
representatives from all of the different disciplines is critical.
“Definitely have a historic preservationist
involved,” says Allen.
Dr. John M. Watts, Jr., a member of the NFPA
914, Recommended Practice for Fire Protection in Historic Structures,
committee, adds, “One of the biggest issues is establishing
communication between the code official or fire safety consultant and
the historic preservation people and interests.”
Dr. Barbara Wolanin, the curator for the
Capitol, agrees.
“Better project coordination in the beginning
is far better than having to make changes at the last minute,” she
says.
When bringing these two groups together, Watts
says that it might appear at first that they’re opposed to one
another. However, “both groups are trying to preserve and protect the
building, one from fire and the other from all the other types of
threats that historic buildings may be exposed to. Remembering that
sometimes helps to get the communications going.”
NFPA 914 is currently a guide, but at the NFPA
2000 Fall Education Conference, the membership is going to vote on
making it a standard.
“NFPA 914 tries to identify a process of
establishing appropriate fire safety in historic buildings,” says
Watts, who is one of NFPA 914’s former chairs. NFPA 914 includes
information on fire experience in historic buildings, identification
and evaluation of existing conditions, planning and design, fire
protection and safe practices in the construction phase, and operations
and maintenance.
NFPA 914 can serve as a bridge between the code
official and the historic preservationist. While both want to preserve
historic buildings from damage, the two disciplines may seem to differ
on how to go about this. The historic preservationist doesn’t want to
do any work that will alter the historic character of the building,
while “the code official says it has to conform with every other kind
of building and might not appreciate the distinctiveness of the
cultural heritage,” says Watts. It’s important to be creative and
not apply a cookie-cutter approach to fire safety in historic
buildings.
Ensuring that fire doesn’t damage any of our
nation’s historical treasures is an ongoing and complex challenge.
Implementing fire protection plans in such a way as not to damage
irreplaceable works of art or the building itself provides additional
challenges to the engineers and workers in the Capitol. Through the
creative use of new and existing technology, however, the safety of
such a significant national landmark and that of the workers and
visitors is being improved.
Ed Comeau is the principal writer for
writer-tech.com, a technical writing firm. He is the former chief fire
investigator for NFPA and has worked with ATF on a number of incidents.
He has been closely involved in the development of interFIRE VR from
its inception and is a member of its web site editorial review board.
|